ARRESTER->ARRESTER-14-1

 

Technical data of 110-220kV zinc surge arresters

Arrester Type

μsystem voltage (r.m.s)

kV

Arrester rated voltage (r.m.s)

kV

Arrester continuous operating voltage (r.m.s)kV

DC reference voltage U1mA not less kV

1/5μs
steepest
wave residual voltage 10kAnot exceeding

kVp
8/20
μs lightning  residual voltage
10kA not exceeding

kVp
30/60μs switching  residual voltage
0.5A not exceeding

2ms rectangular current  withstand discharge capacity A

4/10 μs  current impulse withstand Discharge capacity kA

Resistive
current at continuous operating
voltage

not
exceeding

Y10wZ6-96/250(W.G)

110

96

75

140

280

250

213

600

100

300

Y10wZ6-100/260(W.G)

110

100

78

145

291

260

221

600

100

300

Y10wZ6-102/266(W.G)

110

102

79.6

148

297

266

226

600

100

300

Y10wZ6-108/281(W.G)

110

108

84

157

315

281

239

600

100

300

Y10wZ6-192/500(W.G)

220

192

150

280

560

500

426

600

100

300

Y10wZ6-200/520(W.G)

220

200

156

290

582

520

442

600

100

300

Y10wZ6-204/532(W.G)

220

204

159

296

594

532

452

600

100

300

Y10wZ6-216/562(W.G)

220

216

168.5

314

630

562

478

600

100

300