MAIN DIMENSTIONS AND STANDARD PARTICULARS
|
Cat.No. |
VKS35-S |
VKS35-N |
PS-15/500 |
PSH1-20/125 |
|
Leakage distance/in mm |
900 |
720 |
375 |
520 |
|
Dry arcing distance/in mm |
|
|
|
260 |
|
Cantilever strength/1b kN |
8 |
8 |
13 |
125 |
|
Average flashover voltage |
Low-frequency |
Dry/kV |
100 |
100 |
80 |
90 |
|
Wet/kV |
70 |
70 |
60 |
65 |
|
Critical impulse |
Positive/ kV |
170 |
170 |
|
150 |
|
Negative /kV |
|
|
|
|
|
Radio-influence voltage data |
Test voltage to ground /kV |
|
|
|
22 |
|
Maximum RIV at 1.000kc /μV |
|
|
|
100 |
MAIN DIMENSTIONS AND STANDARD PARTICULARS
|
Cat.No. |
DA-35022Z |
DA-45011Z |
DA-55011Z |
DA-75007Z |
DA-35022K |
DA-45011K |
DA-55011K |
DA-75007K |
|
Leakage distance/in mm |
10 254 |
14 356 |
22 559 |
29 737 |
10 254 |
14 356 |
22 559 |
29 737 |
|
Dry arcing distance/in mm |
5/127 |
6 1/2 165 |
91/2 241 |
121/4 311 |
5/127 |
6 1/2 165 |
9 1/2 241 |
12 1/2 311 |
|
Cantilever strength/1b kN |
2,800 1,270 |
2,800 1,270 |
2,800 1,270 |
2,800 1,270 |
2,800 1,270 |
2,800 1,270 |
2,800 1,270
|
2,800 1,270 |
|
Average flashover voltage |
Low-frequency |
Dry/kV |
70 |
80 |
110 |
125 |
70 |
80 |
110 |
125 |
|
Wet/kV |
65 |
70 |
100 |
115 |
50 |
60 |
85 |
100 |
|
Critical impulse |
Positive/ kV |
100 |
130 |
180 |
210 |
100 |
130 |
180 |
210 |
|
Negative /kV |
125 |
155 |
205 |
260 |
125 |
155 |
205 |
260 |
|
Radio-influence voltage data |
Test voltage to ground /kV |
15 |
15 |
22 |
30 |
15 |
15 |
22 |
30 |
|
Maximum RIV at 1.000kc /μV |
50 |
100 |
100 |
200 |
50 |
100 |
100 |
200 |
|
Net weight/lb kg |
13/5.9 |
16/7.3 |
22/10.0 |
28/12.7 |
13/5.9 |
15/6.8 |
22/10 |
26/11.8 |
|